cve,link,title,description,vendor,products,score,severity,epss,cisa,article,ransomware,exploited,poc,trended,trended_no_1,published,trended_score CVE-2021-35535,https://securityvulnerability.io/vulnerability/CVE-2021-35535,Insufficient Security Control Vulnerability,"Insecure Boot Image vulnerability in Hitachi Energy Relion Relion 670/650/SAM600-IO series allows an attacker who manages to get access to the front network port and to cause a reboot sequences of the device may exploit the vulnerability, where there is a tiny time gap during the booting process where an older version of VxWorks is loaded prior to application firmware booting, could exploit the vulnerability in the older version of VxWorks and cause a denial-of-service on the product. This issue affects: Hitachi Energy Relion 670 Series 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.3. Hitachi Energy Relion 670/650 Series 2.2.0 all revisions; 2.2.4 all revisions. Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions.",Hitachi,"Relion 670 Series,Relion 670/650 Series,Relion 670/650/sam600-io",8.1,HIGH,0.002219999907538295,false,false,false,false,,false,false,2021-11-04T00:00:00.000Z,0 CVE-2021-35534,https://securityvulnerability.io/vulnerability/CVE-2021-35534,Insufficient Security Control Vulnerability,"Insufficient security control vulnerability in internal database access mechanism of Hitachi Energy Relion 670/650/SAM600-IO, Relion 650, GMS600, PWC600 allows attacker who successfully exploited this vulnerability, of which the product does not sufficiently restrict access to an internal database tables, could allow anybody with user credentials to bypass security controls that is enforced by the product. Consequently, exploitation may lead to unauthorized modifications on data/firmware, and/or to permanently disabling the product. This issue affects: Hitachi Energy Relion 670 Series 2.0 all revisions; 2.2.2 all revisions; 2.2.3 versions prior to 2.2.3.5. Hitachi Energy Relion 670/650 Series 2.1 all revisions. 2.2.0 all revisions; 2.2.4 all revisions; Hitachi Energy Relion 670/650/SAM600-IO 2.2.1 all revisions; 2.2.5 versions prior to 2.2.5.2. Hitachi Energy Relion 650 1.0 all revisions. 1.1 all revisions; 1.2 all revisions; 1.3 versions prior to 1.3.0.8; Hitachi Energy GMS600 1.3.0; 1.3.0.1; 1.2.0. Hitachi Energy PWC600 1.0.1 version 1.0.1.4 and prior versions; 1.1.0 version 1.1.0.1 and prior versions.",Hitachi,"Relion 670 Series,Relion 670/650 Series,Relion 670/650/sam600-io,Relion 650,Gms600,Pwc600",7.2,HIGH,0.0021200000774115324,false,false,false,false,,false,false,2021-11-04T00:00:00.000Z,0 CVE-2019-18253,https://securityvulnerability.io/vulnerability/CVE-2019-18253,,"An attacker could use specially crafted paths in a specific request to read or delete files from Relion 670 Series (versions 1p1r26, 1.2.3.17, 2.0.0.10, RES670 2.0.0.4, 2.1.0.1, and prior) outside the intended directory.",Hitachi,Relion 670 Series,10,CRITICAL,0.001339999958872795,false,false,false,false,,false,false,2019-11-27T22:05:47.000Z,0 CVE-2019-18247,https://securityvulnerability.io/vulnerability/CVE-2019-18247,,"An attacker may use a specially crafted message to force Relion 650 series (versions 1.3.0.5 and prior) or Relion 670 series (versions 1.2.3.18, 2.0.0.11, 2.1.0.1 and prior) to reboot, which could cause a denial of service.",Hitachi,Relion 650 And 670 Series,7.5,HIGH,0.0010900000343099236,false,false,false,false,,false,false,2019-11-27T22:03:01.000Z,0